The core issue
Why 100 feet changes the sizing equation
Wire sizing has two constraints: ampacity (can the wire carry the current without
overheating?) and voltage drop (does enough voltage reach the load for it to
operate correctly?). For short runs, ampacity is usually the only constraint. For 100-foot runs,
voltage drop almost always forces you to use larger wire than ampacity alone requires.
The physics is straightforward: every foot of conductor has resistance. At 100 feet one-way, the
current travels 200 feet round-trip. The voltage lost across that resistance is
Vd = 2 × I × R × L / 1000, where I is current, R is resistance per
1000 ft, and L is one-way length. Double the distance, double the drop.
The NEC recommends keeping branch circuit voltage drop under 3%, and total (feeder + branch) under
5%. At 120V, 3% is just 3.6 volts. At 240V, 3% is 7.2 volts — which is why higher voltage circuits
are much more forgiving on long runs.
120V vs. 240V
How source voltage affects wire sizing
The same absolute voltage loss represents a very different percentage depending on source voltage:
-
At 120V: a 4V drop is 3.3% — already over the recommended 3% limit. At 100 feet
with any meaningful load, you almost always need to upsize beyond the minimum ampacity wire.
-
At 240V: a 4V drop is only 1.7% — well within limits. The same wire that fails
at 120V may work perfectly at 240V.
This is why, whenever practical, long runs benefit from 240V circuits. A 240V, 20 amp circuit can
use the same 12 AWG wire that would fail voltage drop limits at 120V over 100 feet.
Common scenarios
Typical 100-foot installations
-
Detached garage sub-panel (60A, 240V): 6 AWG copper or 4 AWG aluminum meets
both ampacity and voltage drop. A very common residential feeder run.
-
Outdoor lighting circuit (15A, 120V): needs 10 AWG copper — two full sizes
above the 14 AWG ampacity minimum. This catches many people off guard.
-
Workshop 20A circuit (120V): needs 8 AWG copper. 12 AWG would drop about 5% —
enough to cause tools to run hot or underperform.
-
Well pump (20A, 240V): 12 AWG copper works — the 240V source keeps the drop at
roughly 2.5%, under the 3% target.
-
Barn or outbuilding sub-panel (100A, 240V): 2 AWG copper or 1/0 aluminum for
ampacity, but voltage drop at 100 ft pushes toward 1/0 copper or 2/0 aluminum.
Cost perspective
Upsizing is cheaper than problems
Voltage drop on long runs causes real problems: motors overheat, LED drivers flicker, compressors
fail to start, and sensitive electronics malfunction. The cost of upsizing wire one gauge at 100
feet is typically $50–150 in additional material — far less than a callback, equipment damage, or
failed inspection.
As a practical rule for 100+ foot runs: calculate first, then buy wire. The few
minutes spent running numbers save hours of rework. Use the voltage drop calculator to check your
exact amperage, voltage, material, and run length.
Run your voltage drop calculation