The baseline
Standard wire size for 100 amp service
NEC Table 310.16 provides ampacity ratings that determine the minimum conductor size. For 100 amp
service at 75°C insulation:
- Copper: 1 AWG is rated for 130 amps — comfortably above 100A.
- Aluminum: 1/0 AWG is rated for 120 amps — adequate margin for 100A.
In practice, many electricians and inspectors prefer 1/0 copper or
2/0 aluminum for service entrance conductors. The extra size provides headroom
for voltage drop, future load growth, and meets the more conservative requirements of some local
jurisdictions and utility companies.
Service entrance vs. feeder
Two different sizing contexts
"100 amp service" can mean two different things, and the wiring requirements differ:
-
Service entrance conductors — from the utility meter base to the main breaker
panel. These are typically short (10–20 ft) and sized primarily by ampacity. Voltage drop is
rarely an issue over such short distances.
-
Feeder conductors — from the main panel to a remote sub-panel (detached garage,
workshop, barn, guest house). These runs can be 50–200+ feet and voltage drop becomes the
controlling factor. The NEC recommends that total voltage drop (feeder + longest branch circuit)
stay under 5%, with the feeder portion ideally under 3%.
If you are running a 100 amp feeder to a detached structure, do not just size by ampacity — always
check voltage drop for your specific run length.
Material choice
Copper vs. aluminum for 100 amp service
At the 100 amp level, aluminum becomes a practical and widely used choice. The cost difference is
significant — aluminum service entrance cable (SER) costs roughly 40–50% less than equivalent
copper per foot.
-
Copper (1 AWG or 1/0): smaller diameter, easier to work in tight panels, lower
resistance per foot. Preferred for short runs and when conduit space is limited.
-
Aluminum (1/0 or 2/0): lighter, significantly cheaper, widely accepted for
service entrance and feeder applications. Requires AL-rated terminals and anti-oxidant compound.
Standard practice for residential service entrance.
Most residential 100 amp services use aluminum SER cable (e.g., 2-2-2-4 aluminum for a 100A
service). This is industry standard and universally accepted when properly terminated.
Compare resistance by material
Voltage drop
Long feeder runs: when to upsize
For service entrance conductors (meter to main panel), runs are typically short enough that
voltage drop is negligible. For feeders to sub-panels, voltage drop is the real sizing constraint.
At 100 amps, 240V, with 1 AWG copper:
-
3% drop threshold: reached at approximately 45 feet one-way.
- Stepping up to 1/0 copper extends this to about 55 feet.
-
For runs of 100+ feet, you may need 2/0 or 3/0 copper (or
3/0 to 4/0 aluminum).
Every 100 amp feeder run should be checked with a voltage drop calculator. The cost of upsizing
conductor one step is far less than the cost of undersized wiring causing equipment problems,
nuisance tripping, or failed inspections.
Calculate voltage drop for your feeder